Bidirectional gas mass flow measurement
Flow range -250 … +250 SLPM
Accuracy ±(2.0+0.5FS) % total error band
Analog 0.5 ~ 2.5 Vdc and I2C output
Integrated temperature output, ±2.5 °C
16 bit resolution, 5 msec response time

Ask for a price

The FS1100 is a MEMS thermal mass flow sensor for gases that measures in both directions, from -250 to +250 SLPM. Flow is reported as a linear analog output of 0.5 ~ 2.5 Vdc or over I2C with 16 bit resolution, from a 5 (± 5%) Vdc supply.

The sensor is fitted inline in the gas path, and the same device reports gas temperature alongside the flow, with a temperature accuracy of ±2.5 °C over 0 ~ 50 °C. Response time is 5 msec and warm-up time 500 msec.

Three values define the choice: the range (-250 … +250 SLPM), the output (analog 0.5 ~ 2.5 Vdc or digital I2C), and the error band you can accept, ±(2.0+0.5FS) % with a repeatability of (0.5+0.15FS) %.

Technical data as published in the manufacturer datasheet.

Flow range-250 … +250 SLPM
Accuracy (total error band)±(2.0+0.5FS) %
Repeatability(0.5+0.15FS) %
Turn-down ratio100:1
Response time5 msec
Temperature range-20 ~ +80 °C
Temperature accuracy (0~50°C)±2.5 °C
Working temperature-10 ~ +55 °C
Temperature coefficient±0.12 %/°C
Maximum pressure0.2 MPa
Warm-up time500 msec
Humidity<95 (no condensation) %RH
Analog null shift±30 mVdc
Power supply5 (± 5%) Vdc
Working current~15 (no output load) mA
OutputLinear, Analog: 0.5 ~ 2.5Vdc / Digital: I2C
Resolution16 bit
Maximum overflow300 SLPM
Maximum flow change40 SLPM/sec
Storage temperature-20 ~ +65 °C
Weight23 g
CalibrationAir @ 20°C, 101.325kPa
ComplianceRoHS; REACH
CEIEC 61000-4-2; 4; 8

RELATED PRODUCTS

FS5002 MEMS Mass Flow Sensor

MEMS gas mass flow sensor with 10 sccm full scale Flow range 0 ~ 10 to 1000 sccm, turn-down ratio 100:1 Accuracy ±(2.0+0.5FS) %, response time 5 msec FS5002 8 ~ 15 Vdc, low power FS5002L 2.7 ~ 5.5 Vdc Temperature -25 ~ +85 °C, pressure up to 0.5 MPa Overflow 3000 sccm, RoHS and REACH compliant

FS4001E MEMS Mass Flow Sensor

MEMS gas mass flow sensor, full scale 30 to 1000 sccm Accuracy ±(1.5+0.5FS) %, turn-down ratio 100:1 Response time 65 msec, 4 / 8 / 16 / 33 / 131 selectable 8 ~ 24 Vdc supply, analog 0.5 ~ 4.5 Vdc, RS232 and I2C Working pressure -0.08 ~ +0.5 MPa, temperature -10 ~ +55 °C Hose coupling (barbed) port, 15 g, RoHS and REACH compliant

FS4308 MEMS Mass Flow Sensor

Compact MEMS gas mass flow sensor, 2 to 50 SLPM Accuracy ±(1.5+0.15FS) %, repeatability 0.5+0.05FS % Analog 1 ~ 5 Vdc, RS485 Modbus, RS232 or I2C Maximum pressure 0.8 MPa, protection class IP40 R 1/4" BSPT or 4 / 6 / 8 mm one-touch fittings Working temperature -10 to +60 °C, response time 10 msec

FS5001E MEMS Mass Flow Sensor

MEMS thermal mass flow sensor for manifold installation Full scale 200 sccm to 15000 sccm, up to 15 SLPM Accuracy ±(2.0+0.5FS) %, turn-down ratio 100:1 Analog 0.5 ~ 4.5 Vdc or I2C output, 8 ~ 24 Vdc supply Pressure range -0.08 ~ 0.5 MPa, burst pressure 1.0 MPa Stainless steel mounting plate and O-rings included

RELATED PRODUCTS